article · 2020 IEEE PES/IAS PowerAfrica
This paper presents voltage stability analysis and improvement of power system when there is increase in wind power penetration. Loading parameter-Voltage curve was used to calculate the loadability and the megawatt margin as the penetration level (PL) of Squirrel Cage Induction Generator Wind System (SCIG-WS) increases. Furthermore, the effects of increasing SCIG-WS PL on grid losses and equipment loading have been investigated. The results show that for the IEEE 14-bus system utilised as case study, the maximum SCIG-WS PL obtainable without reactive power compensation is 49.45%. However, increasing PL has considerable overloading effects on critical transmission lines and generators, which therefore limits the permissible PL to 33.73%. The results also indicate that the application of Static Var System (SVS) yields a significant enhancement in system loadability and reduction in power losses of the system.
This page summarises published work. The authoritative version sits with the publisher.
DOI: 10.1109/powerafrica49420.2020.9219803
Is something wrong with this record? Report it or request removal.
Discussion
Have you built on this work, tried to replicate it, or seen it applied in practice? Share what you know. Verified researchers and MARATTO™ domain experts can open a discussion, and any member can reply. Contributions are reviewed before they appear.
No discussion yet. Open the first thread.
New to MARATTO™? Create a free account.