article
In this work analysis is carried out of the potential of integrating the centralized grid with decentralized renewable energy systems. A techno-economic analysis is done using HOMER Pro for a peri-urban area in Mukono, Uganda. An evaluation of the technical performance for off-grid, grid-connected and grid extension scenarios is performed, assuming the same equipment capacities as the solar PV, battery and generator hybrid system deployed at the mini-grid site. The renewable fraction is 55% for the off-grid and 65% for the on-grid electrification cases. The lowest levelized cost of energy (LCOE) is for the on-grid scenario when no grid installation costs are considered, followed by the grid extension case and with the highest LCOE of US $ 0.274 / kWh being for the off-grid case due to significant generator costs. A sensitivity analysis done for a shorter project lifetime and higher allowed capacity shortfall results elevates the grid extension LCOE to the highest value of US $ 0.300 / kWh.
This page summarises published work. The authoritative version sits with the publisher.
DOI: 10.1109/sustech60925.2024.10553436
Is something wrong with this record? Report it or request removal.
Discussion
Have you built on this work, tried to replicate it, or seen it applied in practice? Share what you know. Verified researchers and MARATTO™ domain experts can open a discussion, and any member can reply. Contributions are reviewed before they appear.
No discussion yet. Open the first thread.
New to MARATTO™? Create a free account.