MARATTO

article · Energies

Ground Resistance Estimation for a DC Converter Station: Theory versus Experiment

20244 citationsOpen accessBeni Suef University

Abstract

This paper is aimed at proposing a calculation model for the ground resistance of a grounding scheme servicing a high-voltage direct-current converter station. The method is based on the equivalence of current conduction and electric field from the grounding scheme through the surrounding medium. The grounding scheme is composed of three concentric ring electrodes supported by two horizontal conductors and eight vertical rods. The calculated ground resistance is 4.8 Ω against the experimental value of 5 Ω with an error of 4.2%. The calculated ground resistance value agrees reasonably well with that of 4.7 Ω as obtained using CYMGRD software (version 7.0). The calculated surface-potential values over the ground surface agreed reasonably well with those measured experimentally, with an average deviation not exceeding 6.5%. This study is designed to investigate how ground resistance is decreased by the increase in the scheme parameters, including the rods’ diameter and length, as well as the radius of the inner and outer rings. The dependency of the ground resistance on the soil type is also investigated.

Research topics

  • Lightning and Electromagnetic Phenomena
  • Electromagnetic Compatibility and Noise Suppression
  • Thermal Analysis in Power Transmission

Sustainable Development Goals

Read the original research

This page summarises published work. The authoritative version sits with the publisher.

DOI: 10.3390/en17040765

Is something wrong with this record? Report it or request removal.

Discussion

Discuss this research

Have you built on this work, tried to replicate it, or seen it applied in practice? Share what you know. Verified researchers and MARATTO™ domain experts can open a discussion, and any member can reply. Contributions are reviewed before they appear.

No discussion yet. Open the first thread.